95
OCH722A
(From the previous page.)
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default
setting
Field
setting
Notes
Setting
Service
menu
Operation set
-
tings
Smart grid
ready
DHW
On/Off
Off
Target temp (+1 to +20°C) / -- (Non active)
--
Heating
On/Off
Off
Target temp.
Switch-on recommendation (20 to 60°C)
50°C
Switch-on command (20 to 60°C)
55
°C
Pump cycles
Heating (On/Off)
On
Interval (10 to 120 min)
10 min
Floor dry up function
On/Off *2
Off
Target temp.
Start&Finish (20 to 60°C)
30°C
Max. temp. (20 to 60°C)
45°C
Max. temp. period (1 to 20 days)
5 days
Flow temp. (In
-
crease)
Temp. increase step (+1 to +10°C)
+5°C
Increase interval (1 to 7 days)
2 days
Flow temp. (De
-
crease)
Temp. decrease step (−1 to −10°C)
−5°C
Decrease interval (1 to 7 days)
2 days
Summer mode
On/Off
Off
Outdoor ambient
temp.
Heating ON (4 to 19°C)
10°C
Heating OFF (5 to 20°C)
15
°C
Judgement time
Heating ON (1 to 48 hours)
6 hours
Heating OFF (1 to 48 hours)
6 hours
Forced heating ON (−30 to 10°C)
5
°C
Water flow control
On/Off
Off
Energy monitor settings
Electric heater
capacity
Booster heater 1
capacity
0 to 30kW
2kW
Booster heater 2
capacity
0 to 30kW
4kW
Immersion heater
capacity
0 to 30kW
0kW
Analog output
0 to 30kW
0kW
Delivered energy adjustment
−50 to +50%
0%
Water pump
input
Pump 1
0 to 200W or ***(factory fitted pump)
***
Pump 2
0 to 200W
0W
Pump 3
0 to 200W
0W
Pump 4
0 to 200W
72W
Electric energy meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
Heat meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
External input settings
Demand control (IN4)
Heat source OFF/Boiler operation
Boiler
operation
Outdoor thermostat (IN5)
Heater operation/Boiler operation
Boiler
operation
Thermo ON output
Zone1/Zone2/Zone1&2
Zone1&2
*1 The settings related to Zone2 can be switched only when 2 zone temperature control is enabled (when DIP SW2-6 and SW 2-7 (FTC) are ON).
*2 On: the function is active; Off: the function is inactive.
*3 When DIP SW1-1 (FTC) is set to OFF “WITHOUT Boiler” or SW2-6 (FTC) is set to OFF “WITHOUT Mixing tank”, neither Boiler nor Hybrid can be selected.
*4 Valid only when operating in Room temp. control mode.
*5 “*” of “*/kWh” represents currency unit (e.g. € or £ or the like)
*6 Valid only when operating in Heating room temperature.
*7 If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk)
*8 The settings related to Zone2 can be switched only when 2-zone temperature control or 2-Zone valve ON/OFF control is active.
*9 When DIP SW5-2 (FTC) is set to OFF, the function is active.
*10 Do not change the setting since it is set according to the specification of flow sensor attached to the heat pump unit.