69
OCH722A
(2) Function of switches (Controller circuit board)
DIP switch
Function
OFF
ON
Effective timing
Default
settings
SW1 SW1-1
—
—
―
—
OFF
SW1-2
Abnormal history clear
Normal
Clear
Always
OFF
SW4 SW4-1
—
—
―
—
OFF
SW4-2
—
—
―
—
OFF
SW5 SW5-1
—
—
―
—
OFF
SW5-2
Power failure automatic recovery*1
No auto recovery Auto recovery When power supply ON
ON
SW5-3
—
—
—
—
OFF
SW5-4
—
—
―
—
OFF
SW5-5
—
—
—
—
OFF
SW5-6
—
—
―
—
OFF
SW6
SW6-1
Brine pump manual operation
Pump OFF
Pump ON
Always (ONLY Brine pump
manual operation)
OFF
SW6-2
—
—
—
―
OFF
SW6-3 Brine pump manual operation
Inactive
Active
When power supply ON
OFF
SW6-4
Model select
Heat pump setting
―
ON
SW6-5
ON
SW6-6
OFF
SW6-7
ON
SW6-8
OFF
SW7
*2
SW7-1
—
—
—
―
OFF
SW7-2
—
—
—
―
OFF
SW7-3
—
—
—
―
OFF
SW7-4
—
—
—
―
OFF
SW7-5
—
—
—
―
OFF
SW7-6
Starting brine temp. of borehole freeze prevention
−2°C
0°C
Always
OFF
SW8
SW8-1
Brine pump speed adjustment
See Installation manual '4.4
Brine Pipe Works'
Always
OFF
SW8-2
—
—
—
―
OFF
SW8-3
—
—
—
―
OFF
SW9 SW9-1
Brine pump rotational speed adjustment
See Installation manual '4.4
Brine Pipe Works'
Always
OFF
SW9-2
OFF
SW9-3
OFF
SW9-4
OFF
<Table 9.8.2>
Note:
*1 “Power failure automatic recovery” can be set by either remote controller or this DIP SW. If one of them is set to ON,
“Auto recovery” activates.
*2 Please do not use SW7-3, 4 usually. Trouble might be caused by the usage condition.