SW2 setting
Display detail
Explanation for display
Unit
<Heat pump unit operation monitor function>
[When optional part “A-Control Service Tool (PAC-SK52ST)” is connected to Controller circuit board (CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by controlling
DIP SW2 on “A-Control Service Tool”.
Operation indicator SW2 : Indicator change of self diagnosis
1
ON
2 3 4 5 6
<Digital indicator LED1 working details>
(Be sure that 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON
When the power supply ON, blinking displays by turns.
Wait for 4 minutes at the longest.
(2) When the display lights (Normal operation)
1
Operation mode display
1
ON
2 3 4 5 6
(Initial setting)
SW2
1 second
interval
LED1
(Lighting)
Display
Operation Model
The tens digit : Operation mode
The ones digit : Relay output
O
H
Display
0
1
2
3
4
5
6
7
8
A
Compressor
Warming-up
Compressor
—
—
—
—
ON
ON
ON
ON
—
—
—
—
—
—
—
—
—
—
ON
ON
OFF / pump
HEATING
2
Display during error postponement
Postponement code is displayed when
compressor stops due to the work of
protection device.
Postponement code is displayed while
error is being postponed.
(3) When the display blinks
Inspection code is displayed when compressor stops due to the work of protection devices.
Display Contents to be inspected (When power is turned on)
F3
F5
F9
E8
E9
EA
Eb
EC
EE
E0–E7
63L connector(red) is open.
63H connector(yellow) is open.
2 connectors(63H/63L) are open.
FTC/Controller circuit board communication error (Signal receiving error) (Controller circuit board)
FTC/Controller circuit board communication error (Transmitting error) (Controller circuit board)
Miswiring of FTC/Controller circuit board unit connecting wire
Miswiring of FTC/Controller circuit board unit connecting wire(converse wiring or disconnection)
Startup time over
Incorrect connection
Communication error except for controller circuit board
Display Inspection circuit board
0
1
Controller circuit board
FTC
Display
Contents to be inspected (During operation)
U1
U2
U3
U4
U5
U6
U7
U8
Ud
UF
UH
UL
UP
P1–P8
Abnormal high pressure (63H operated)
Abnormal high discharge temperature, high comp. surface temperature,
shortage of refrigerant
Open/short of heat pump unit thermistors (TH4, TH33)
Open/short of heat pump unit thermistors (TH3, TH32, TH34, TH7 and TH8)
Abnormal temperature of heat sink
Abnormality of power module
Abnormality of superheat due to low discharge temperature
Abnormality in brine pump motor
Overheat protection
Compressor overcurrent interruption (When Comp. locked)
Current sensor error
Abnormal low pressure
Compressor overcurrent interruption
Abnormality of FTC
The black square (
■
) indicates a switch position.