Model
Outline
Weight
Applicable crimping terminal
A6TBXY36
A6TBXY54
A6TBX70
A6TBX36-E
A6TBX54-E
A6TBX70-E
A6TBY36-E
A6TBY54-E
1.25-3.5 (JIS)
1.25-YS3A (J.S.T.)
V1.25-M3 (J.S.T.)
V1.25-YS3A (J.S.T.)
2-3.5 (JIS)
2-YS3A (J.S.T.)
V2-S3 (J.S.T.)
V2-YS3A (J.S.T.)
Applicable
wire size
0.75 to
2 mm
2
Model
Outline
Weight
Applicable model
AC05TB
0.5 m, for sink type modules
A6TBXY36
A6TBXY54
A6TBX70
A6TBX36-E
A6TBY36-E
A6TBX54-E
A6TBY54-E
A6TBX70-E
0.17 kg
AC10TB
1 m, for sink type modules
0.23 kg
AC20TB
2 m, for sink type modules
0.37 kg
AC30TB
3 m, for sink type modules
0.51 kg
AC50TB
5 m, for sink type modules
0.76 kg
AC80TB
8 m, for sink type modules (common current: 0.5 A or lower)
1.2 kg
AC100TB
10 m, for sink type modules (common current: 0.5 A or lower)
1.5 kg
AC05TB-E
0.5 m, for source type modules
0.17 kg
AC10TB-E
1 m, for source type modules
0.23 kg
AC20TB-E
2 m, for source type modules
0.37 kg
AC30TB-E
3 m, for source type modules
0.51 kg
AC50TB-E
5 m, for source type modules
0.76 kg
Specifications
Cables
A6TBXY36 (for 32 points)
Width
(All models have the same height and depth)
D=52 mm
W=120 mm
H=78.5 mm
A6TBXY36
A6TBXY54
A6TBX70
120 mm
155 mm
190 mm
Connector/terminal block converter module
The following is an example of replacing contact output modules (AY13) with transistor output modules (QY41P)
and externally converting transistor outputs into contact outputs.
●
Instructions
Replace AY13 with QY41P and connect the relay terminal modules to convert to contact outputs.
With this method, the system can be upgraded without increasing the number of modules on the base unit.
Also, 8 points/common, the same specification as that of the AY13, can be maintained.
Q61P
Q01UCPU
QX41
QX41
QX41
QX41
QX42
Q61P
QY41P
QY41P
QY41P
QY41P
QY41P
A61P
A2NCPU
AX41
AX41
AX41
AX41
AX42
A61P
AY13
AY13
AY13
AY13
AY13
X00... X20... X40... X60... X80...
YC0... YE0... Y100...Y120...Y140...
A35B
A65B
QY41P
16-point relay terminal module x 2
(A6TE2-16SRN)
Dedicated cable
(AC
�
TE)
Reray terminal module Reray terminal module
8 points/common
(the same specification
as that of AY13)
• Using the relay terminal modules, a large type A (Large Type) Series 32-point contact output
module can be replaced while maintaining 8 points/common.
• A wide variety of compatible wire sizes are available using the relay terminal module.
A (Large Type) Series 32-point contact output module AY13: Max. 2 mm
2
Relay terminal module: Max. 1.25 mm
2
Q Series 16-point contact output module QY10: Max. 0.75 mm
2
• Replacement is possible without the need of additional modules because a module mounted on
the base unit becomes compatible with 32-point connector type modules through the use of the
"connector/terminal block converter module".
Solution and Benefit
(a) System configuration example
Current configuration
After replacement
Replace
(2) Replace 32-point contact output type module using "relay terminal module"
For positive common input modules and sink output modules (standard type)
For positive common input modules and sink output modules (2-wire type)
For positive common input modules (3-wire type)
For negative common input modules (standard type)
For negative common input modules (2-wire type)
For negative common input modules (3-wire type)
For source output modules (standard type)
For source output modules (2-wire type)
0.4 kg
0.5 kg
0.6 kg
0.4 kg
0.5 kg
0.6 kg
0.4 kg
0.5 kg
31
2.1 Replace A/QnA (Large Type) Series with Q Series