* The extension stage number of the QA conversion adapter
should be set in accordance with that of the extension base unit.
Power supply module (Q Series new)
Product name
Power supply module (for extension base unit)
Extension base unit
Input module
Output module
*1: Select the module depending on the existing program capacity and contents.
*2: Used to mount the Q Series CPU.
*3: Used to mount modules on the existing main base unit.
*4: Select the cable length according to the arrangement of base units.
Extension base unit (1st stage)
Main base unit
CPU module
Existing module
Replacement module
N/A
A61P (main/extension base unit)
A65B
N/A
A35B
A3ACPU
1
-
-
1
Extension cable
QA conversion adapter module
N/A
N/A
Q61P
Utilize existing module
Utilize existing module
Use existing module in original state
Use existing module in original state
QA65B*
3
Q35B*
2
Q03UDCPU*
1
QC06B*
4
QA6ADP
3
2
1
1
-
3
2
-
-
-
1
1
• The existing A (Large type) Series extension base unit and mounted modules can be utilized without wiring
modification.
The existing A (Large Type) Series extension base unit can be used without modifying the wiring by repl
acing
with the extension base QA6�B, and remounting the mounted modules.
• Prog
ram modifications can be minimized by using the same I/O address for the existing units and setting the
current I/O addresses with the parameter I/O assignments.
•
The follo
wing A (Large Type) Series module cannot be used with the Q Series CPU. These must be changed
to a Q Series CPU compatible module.
CC-Link master/local module
MELSECNET/10 network module
Ethernet module
Ethernet module, computer link module
etc.
• The A (Large Type) Series A6�B/A5�B extension base unit with the QA6ADP cannot be used together with
the QA1S6�B extension base unit.
• When an AC input module is mounted on the "A5�B" extension base unit (without power supply) using the
QA6ADP, either the "A6�B with QA6ADP" or "QA6�B" extension base unit (with power supply) is required in
the system.
• Set th
e stage number for QA6ADP according to the setting of the extension base unit.
• The Q
A6ADP QA conversion adapter is only compatible with High Performance Model QCPU or Universal
Model QCPU (first five digits of serial No. "13102" or higher).
Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs, and Remote I/O Stations are not
compatible.
• For the precautions and restrictions when using QA conversion adapter, refer to "QA6ADP QA Conversion
Adapter Module User's Manual".
A35B
A61P
A3ACPU
AX42
X00...
AX42
AX42
AX42
AX42
Q61P
Q03UD CPU
Q35B
The QA conversion adapter module enables the existing extension base, including the mounted I/O
modules, to connect to a Q Series main base unit. This can shorten the installation and wiring
modification times.
Solution and Benefit
The following is an example of reusing existing A (Large Type) Series modules with a Q Series CPU using the
QA conversion adapter module.
●
Instructions
(1) Replace the A (Large Type) Series CPU with the Q Series CPU (Q03UDCPU) and mount it on the Q Series
main bas
e unit (Q3�B).
(2) To reutilize I/O modules mounted on the existing A
(Large Type) Series main base unit, mount them on the
QA6�B extension base unit.
(3) Mount the “QA6ADP” adapter on the connector of each existing extension base unit to allow the use
of existing modules.
(4) Connect the base units with the Q Series extension cable (QC�B).
A65B
A61P
AX41
X140...
AY42
AX41
AY42
AY42
Extension base stage 1
A65B
A61P
Extension base stage 2
AY42
Y240...
AY42
AY42
AY41
AY41
QA65B
A61P
AX42
X00...
AX42
AX42
AX42
AX42
Extension base stage 1
A65B
A61P
Extension base stage 2
AX41
AY42
AX41
AY42
AY42
A65B
A61P
Extension base stage 3
AC06B
AC06B
QC06B
QC06B
QC06B
AY42
AY42
AY42
X140...
*
*
Y240...
AY41
AY41
QA6
ADP
QA6
ADP
Replace the A (Large Type)
CPU with a QCPU
Utilize the modules
and extension base unit.
Utilize the modules
and extension base unit.
The adapter allows the A (Large Type) Series extension base unit to be
used as the QCPU's extension base unit. (Max. 7 extension stages)
Remount the
modules on the
QA6
�
B.
Q Series modules
are mountable
Current configuration
After replacement
●
Module selection example
(1) System configuration example
Tip
Extension stage
number setting: 2nd stage
Extension stage
number setting: 3rd stage
3.1.2 Utilize existing I/O modules and extension base unit with Q Series CPU
(Use QA conversion adapter)
74
3.1 Replace A/QnA (Large Type) Series with Q Series