(2) Method for maintaining existing addresses
The existing addresses can be maintained by transferring transmitted and received data by FROM/
TO instructions for each station without auto refresh setting.
The CC-Link communication conditions including the station information must be set by the
parameters.
(3) FROM/TO instructions sample program for transfer of transmitted and received data
(1) Address allocation table
Buffer memory
address on input
side
Buffer memory
address on
output side
Model name of
replacement
module
Devices to be
used by FROM/
TO instructions
Device to be used for
auto refresh setting
Station No.1
E0
AJ65SBTB2N-16A
X100 to 10F
X100 to 11F
(X110 to 11F: Not in use)
E1
Station No.2
E2
AJ65SBTB2N-16A
X110 to 11F
X120 to 13F
(X130 to 13F: Not in use)
E3
Station No.3
E4
AJ65DBTB1-32D
X120 to 13F
X140 to 15F
E5
Station No.4
E6
AJ65SBTB3-16D
X140 to 14F
X160 to 17F
(X170 to 17F: Not in use)
E7
Station No.5
E8
AJ65SBTB2N-16A
X150 to 15F
X180 to 19F
(X190 to 19F: Not in use)
E9
Station No.6
16A
AJ65SBTB2N-16R
Y160 to 16F
Y1A0 to 1BF
(Y1B0 to 1BF: Not in use)
16B
Station No.7
16C
AJ65DBTB1-32R
Y170 to 18F
Y1C0 to 1DF
16D
* Sample program
Data transfer
Command 1
Data transfer
Command 2
Receipt of input data to the first module mounted in place of
the existing AX11C
Receipt of input data to the second module mounted in place
of the existing AX11C
Receipt of input data to the module mounted in place of
the existing AX41C
Receipt of input data to the module mounted in place of
the existing AJ35TB2-16D
Receipt of input data to the module mounted in place of
the existing AX10Y10C on the input side
Sending of output data from the module mounted in place of
the existing AX10Y10C on the output side
Sending of output data from the module mounted in place of
the existing AY13C
153
7.5 Method for maintaining existing addresses when replacing MELSECNET/MINI(-S3) with CC-Link