7.6 Replace pulse catch module
There are no available replacement modules for AnS (Small Type) Series pulse catch module A1SP60.
Replace it with one of the followings.
•‥L‥Series‥CPU‥:‥Built-in‥I/O‥pulse‥catch‥function
•‥Q‥Series‥CPU:‥Interrupt‥module‥QI60
7.6.1 Replace with LCPU built-in I/O pulse catch function
The address of the LCPU built-in I/O pulse catch function is determined by the I/O assignment
parameter and the built-in I/O function setting. Therefore, it is necessary to change the existing
address Xn to the address set for the LCPU built-in I/O pulse catch function.
●
Replacement example
Example of existing configuration
Example of new configuration
Replace
A1S
61PN
A1SH
CPU
A1S
P60
I/O
module
I/O
module
I/O
module
The address depends on the module position
(16 points occupied).
L02CPU
L61P
I/O
module
I/O
module
I/O
module
The address (16 points occupied) and built-in
I/O function are set by the PC parameters.
(1) Example of LCPU parameter setting
The following parameters must be set to use the LCPU built-in I/O function.
Select "L parameter setting" -> "I/O assignment setting," and set the first XY to 0.
Select
"
L parameter setting
"
->
"
Built-in I/O function setting,
"
and specify the pulse catch function
for the input signal Xn0.
154
7.6 Replace pulse catch module