(2) When the load capacity of externally connected device is 0.6 A to 1 A
Select the transistor output module QY40P/QY41P as a replacement module, and externally
provide the FA goods manufactured by Mitsubishi Electric Engineering Co., Ltd. to increase the
load capacity.
QCPU
QY40P QY40P
Q35B
FA-CBL
**
TMV20
FA-CBL
**
TMV20
ACPU AY22 AY22
A35B
Replacement example(1)
Replacement example(2)
FA-TH16YSR11S
FA-TH16YSR11S
QCPU
QY41P
Q35B
FA-CBL
**
FM2V
FA-TH16YSR11S
FA-TH16YSR11S
Power
supply
module
Power
supply
module
Power
supply
module
Empty
(3) When the load capacity of externally connected device is 1 A or more and Triac output is
necessary for reasons of specifications
Select the transistor output module QY40P/QY41P as a replacement module, and externally
provide a commercially available Triac conversion terminal module to increase the load
capacity. (We do not introduce any product.)
(4) When the load capacity of externally connected device is 1 A or more and a change to relay
output can be made for reasons of specifications
Select QY10 as a replacement module, and use the conversion adapter ERNT-AQTY10 to use
the existing module terminal block without modifying the wiring.
ACPU AY22 AY22
Q35B
QCPU
ERNT-
AQT
Y10
ERNT-
AQT
Y10
QY10
QY10
A35B
Replacement example
Power
supply
module
Power
supply
module
185
10.2 Notes for selection of replacement for Triac output module AY22