95
10.2
Security Industries Association SIA Format Protocol FX-
3500RCU Series Event Codes
SIA Format Protocol does not define indicating zone troubles, but lists it as Untyped Zone
Trouble/Restore.
Table 21 SIA-DCS Event Codes
Event Description
Event Family Qualifier
SIA Event Code Parameter
Phone Line #1 trouble detected
Trouble
New event
LT
001
Phone Line #2 trouble detected
Trouble
New event
LT
002
Phone Line #1 trouble restored
Trouble
Restore
LR
001
Phone Line #2 trouble restored
Trouble
Restore
LR
002
Failure to report to an Account
Trouble
New event
YC
Acct #
Report to an Account successful
Trouble
Restore
YK
Acct #
RS485 Communication Trouble
Trouble
New event
YS
485
Periodic (24 hr) Test Event (Normal)
Test
New event
RP
000
Periodic (24 hr) Test Event (Off-normal) Test
New
event
RY
000
Manually initiated dialer test
Test
New event
RX
000
Zone Fire Alarm
Alarm
New event
FA
NNN
Zone Fire Alarm restored
Alarm
Restore
FH
NNN
Zone Trouble detected
Trouble
New event
FT
NNN
Zone Trouble restored
Trouble
Restore
FJ
NNN
Zone Supervisory condition
Supervisory
New event
FS
NNN
Zone Supervisory restored
Supervisory
Restore
FR
NNN
Water flow alarm
Alarm
New event
WA
NNN
Water flow alarm restored
Alarm
Restore
WH
NNN
General Alarm
Alarm
New event
QA
NNN
General Alarm restored
Alarm
Restore
QH
NNN
Indicating Zone Trouble (*)
Trouble
New event
UT
NNN
Indicating Zone Trouble restored (*)
Trouble
Restore
UR
NNN
AC power lost
Trouble
New event
AT
000
AC power restored
Trouble
Restore
AR
000
Battery Low
Trouble
New event
YT
000
Battery Low restored
Trouble
Restore
YR
000
Ground Fault
Trouble
New event
YP
000
Ground Fault restored
Trouble
Restore
YQ
000
Summary of Contents for FX-3500RCU
Page 2: ......