41
How to Enable or disable the Positive Alarm Sequence
1. From the Keypad of the FACP press
M
to enter the
Menu
.
2. Using
the
Up and Down
cursor buttons, scroll to
Operation
.
3. Press
Enter.
4. In
the
Operation Menu
scroll to
Positive Alarm
.
5. Press
Enter
.
You will now see the current status of the
Positive Alarm Sequence
and will be
prompted to change status.
Figure 13 Enabling the Positive Alarm Sequence
6. To change the status press
Enter
.
7. To exit without changing the status press
Cancel
.
5.9
Remote Annunciator Operation
The FX-3500RCU System supports the following types of annunciators
•
RAX-LCD-LITE shared display annunciator.
•
RAM-3500-LCD shared display annunciator.
•
Conventional LED/switch annunciators.
Both types of annunciators are connected to the panel via the RS-485 serial link.
The maximum number of annunciators is seven (7). Configuration of the annunciators is done
via the software Configurator.
Ensure that the address DIP switch on each annunciator is set to the same value set in the
Configurator. Only the first three (3) DIP switches are used for address configuration.
Note:
There will be no notification message advising a change of status.
Table 10 Annunciator Address DIP Switch Settings
Address
SW1-1
SW1-2
SW1-3
1
ON
OFF
OFF
2
OFF
ON
OFF
3
ON
ON
OFF
4
OFF
OFF
ON
5
ON
OFF
ON
6
OFF
ON
ON
Pos Alarm disabled
Enable? Y
i