7.4.3
UL 864 10th Edition Addressable Supervised Output Module Wiring
As per UL 864 10th edition section 56.4.3, ensure that a single break, ground or wire-to-wire
fault on the installation conductors of a signalling circuit for use with addressable notification
appliances or modules shall not affect the operation of more than one notification zone.
Exception: Riser conductors installed in accordance with the survivability from attack by fire
requirements in National Fire Alarm Code, NFPA 72.
7.4.4
RTI-1 Common Remote Trouble Indicator Wiring
Figure 23 RTI-1 Common Remote Trouble Indicator Wiring
WIRE NUT
CONNECTION
RTI-1
Current: 30mA maximum
Voltage: 24V
Frequency: 20 pulses per minute (ppm)
Power Factor: 1
Use 20 AWG or larger
Maximum wiring distance of 4000 feet
RTI
+ -
TRL TRB
UNFLTD