35
Addressable
/
Analog Device Verification Process
If the system is not already in alarm:
1. A device entering into alarm initiates a 30 second delay timer.
2. When the 30 second delay times out the device is monitored for the next 60 seconds.
3. If the same device enters into alarm again during this time the alarm is confirmed. The
following will also confirm the alarm:
•
Any additional Alarm Input activating aborts the verification process and confirms the
alarm.
•
Any trouble detected on the circuit being verified aborts the verification process and
confirms the alarm.
LED Indication
The Alarm Zone LED indicator flashes for the duration of the verification process. If the alarm
is not confirmed the LED turns off. If the alarm is confirmed the LED illuminates steady.
5.3
Output Types
Output devices and modules may be configured as one of many possible output types. Table 9
identifies the device types assignable to each output type. For device type descriptions see
sections 5.3.1 to 5.3.4.
Output modules on the addressable/analog loop may be configured as any of the following
output types:
•
Signals
•
Strobes
•
Relay outputs
•
Hazard Release
Additional Operation Features
•
Regarding CLIP devices, once the FACP activates the sensor LED, an attached Relay/
Sounder base and any Remote Devices wired to the base are also activated.
Suppressing the device LED via the NF flag in the Configurator means the Relay/
Sounder base and any Remote devices wired to the base will not activate.
Note:
Conventional smoke detectors cannot utilize alarm verification with M502(AP)
zone modules.
Table 9 Configurable Output Types
Output Type
As listed in
Configurator
Description
located in
Section
number
Device Types
Relay Output
Module
Supv Output
Module
Hazard Release
Haz Release
5.3.1
X
Relay
Relay
5.3.4
X
X
Signal
Signal
5.3.2
X
X
Strobe
Strobe
5.3.3
X
X
i