Configuration with the CFG-300 LCD Service Tool
11.15 Zone messages
Point annunciation is indicated on the LCD display. There are no separate queues for
TROUBLE, ALARM, SUPERVISORY and BUILDING; instead there is only one queue that
indicates all the events. The respective TROUBLE, ALARM, SUPERVISORY and BUILDING
LEDs flash if at least one of the given types is in the queue.
The CFG-300 LCD service tool shows only the first alarm or trouble. If a trouble happens first
and then an alarm happens, the alarm appears. Any further events change the total number of
events, shown in the right hand corner of the LCD display. The order of priority is alarm,
supervisory, trouble and property and building safety.
11.15.1 Example 1 (detection circuit):
Event 01 of 09,
OPEN TRB
on initiating circuit
Z-01
in the
EAST LOBBY ENTRANCE
with
process type as
VERIFIED ALARM
and the event occurred on
2003/02/02
at
18:01
TUESDAY
.
Figure 53 Detection circuit zone message
11.15.2 Example 2 (indicating circuit):
Event 02 of 09,
SHORT TRB
on indicating circuit
NAC-01
in the
EAST WING LOBBY
with
process type as
SILENCEABLE
and the event occurred on
2003/02/02
at
18:01 TUESDAY
.
Figure 54 Indicating circuit zone message
Other common messages are described below.
E A S T L O B B Y E N T R A N C E
O P E N T R B 0 1 / 0 9
V E R I F I E D A L A R M Z - 0 1
1 8 : 0 1 T U E 2 0 0 3 - 0 4 - 0 4
ZO N E
M essage
E V E N T
01 of 09
Process
Type
Physical
Zone N o.
D AT E
T IM E
"IN FO "
Key
EV E N T
type
E A S T W I N G L O B B Y
S H O R T T R B 0 2 / 0 9
S I L E N C E - A B L E N A C - 1
1 8 : 0 1 T U E 2 0 0 3 - 0 2 - 0 2
"IN FO "
Key
ZO N E
M essage
EV E N T
type
E V E N T
02 of 09
Process
Type
Physical
Zone N o.
D AT E
T IM E