98
Appendix C: Specifications
Ground Fault
Impedance
2 k
Ω
Battery
Type
24VDC Sealed Lead Acid, 12 AH
Charging capability
1.25 Amp
Protection
10A on board (F1) slow blow micro fuse
Compliance
System Model
FA-300 Series LED Version Fire Alarm Control
Panel
System Type
Local, Auxiliary (using PR-300), Remote Protected
Premises Station (using PR-300 or FA-301-12LDR,
FA-301-12LDW, or FA-301-8LDW) Central Station
Protected Premises (using FA-301-12LDR, FA-301-
12LDW, or FA-301-8LDW).
Type of Service
A, M, WF, SS
Type of Signalling
Non-Coded
Applicable Standards
NFPA 70 and 72, UL 864 Rev. 9, ULC-S524, ULC-
S527-11, ULC-S559-13
Table 17
FA-300 LED System Modules and Annunciators
FA-300 LED Series Modules and Annunciators
RM-312/306
Relay Adder Module
Must be connected to a listed power-limited
source of supply.
Contact rating
NO / NC / 28VDC per contact / 1A resistive
load max
Current consumption
standby 0mA, alarm 80mA
ICAC-306
Input Class A Converter module
standby: 0mA / alarm: 0mA
OCAC-304
Output Class A Converter Module
standby: 0mA / alarm: 0mA
OCAC-302
Output Class A Converter module
Standby 0mA / alarm 0mA
SRM-312
Smart Relay Module
Must be connected to a listed power-limited
source of supply
Contact rating
FormC/ 28VDC per contact /
1A resistive load max, zoned
Current consumption
standby 30mA / alarm
140mA
Contact rating
FormC/ 28VDC per contact / 1A resistive load
max, zoned
Current consumption
standby 30mA, alarm 140mA
RAM-300
Remote LCD Annunciator
Standby 56mA / alarm 65mA
RAM-208
8 Zone Remote Annunciator
Standby 35mA / alarm 90mA
Table 16
FA-300 LED Series Specifications (Continued)
FA-300 LED Fire Control Panel Chassis
Summary of Contents for FA-300 Series
Page 2: ......