![background image](http://html1.mh-extra.com/html/mircom/fa-300-series/fa-300-series_installation-and-operation-manual_1805754064.webp)
64
Configuration with the CFG-300 LCD Service Tool
Command Menu/FA-300 Config/Features/
3.Output Circuit Correlation
[X] DISABLE->Default
[ ] ENABLE
Signal correlations
If enabled, the programmed
effective. If disabled, the
programmed correlations are
ignored and all the output circuits
are correlated to all the input
circuits.
Command Menu/FA-300 Config/Features/
4.Waterflow/Sprinkler Retard
Operation
[X] DISABLE ->Default
[ ] ENABLE
Retard waterflow and
sprinkler circuit
If disabled, all the initiating
circuits configured as water flow
or sprinkler act as non-verified
alarms. If enabled, retard
operation is performed for
initiating circuits configured as
water flow or sprinkler.
See 9.7.5 Water Flow Alarm
(Water flow Sensors) on page 51.
Command Menu/FA-300 Config/Features/
5.Aux. disconnect, disconnects
Aux Alarm relay and all
programmed relays
[ ] ENABLE
[X] DISABLE->Default
"Aux Disconnect"
disconnects prog. relay
If disabled, only the Auxiliary
Alarm Relay is disconnected
when you press AUXILIARY
Button on page 48).
If enabled, the Auxiliary Alarm
Relay and all correlated relays
are disconnected when you press
AUXILIARY DISCONNECT (see
Button on page 48). Correlated
relays include: RM312/RM306
relays and SRM-312 relays.
Command Menu/FA-300 Config/Features/
6.Signal-Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Signal silence inhibit
Timer
Use this menu to inhibit the
SIGNAL SILENCE button for a
desired length of time. While this
timer is running, pressing the
SIGNAL SILENCE button has no
According to the Canadian
National Building Code, this timer
should be set to one minute.
Table 14
Feature Config menu
Feature
Default
Name in the
FA-300
Configuration Utility
Description
O p t . C k t . C o r r .
[ X ] D I S A B L E
W a t e r f l o w / S p r k . R e t d
[ X ] D I S A B L E
A u x D i s c P r o g
[ X ] D I S A B L E
S i g - S i l . I n h i b i t T m r
[ X ] D I S A B L E
Summary of Contents for FA-300 Series
Page 2: ......