![background image](http://html1.mh-extra.com/html/mircom/fa-300-series/fa-300-series_installation-and-operation-manual_1805754099.webp)
99
Appendix C: Specifications
PR-300
Polarity Reversal and City Tie Module
City Tie
power limited / 24VDC unfiltered / 250mA max
/14Ohms trip coil
Polarity Reversal
power limited / 24VDC open / 12VDC at
3.5mA / 8.5mA max (shorted)
Polarity Reversal Supv. Terminal
24VDC (normal) / -24VDC (supervisory) / 0V
(trouble)
Polarity Reversal Alarm Terminal
24VDC (normal) / -24VDC (alarm) / 0V
(trouble)
Current Consumption
standby 50mA / alarm 300mA (city tie in use) /
alarm 70mA (city tie not in use)
RTI
Remote Trouble Indicator
Standby 35mA / alarm 35mA
Table 17