32
Field wiring
7.3
Connecting to a 3G4010 Interface Device for Canada
A typical connection is shown in Figure 22. The PCS-100 Passive Communications Interface
Board (sold separately) is required.
For information on Compatible DACR Receivers see 12.0 Appendix A: Compatible
Receivers on page 94.
Figure 22 Connecting an FA-300 FACP to a 3G4010 Interface Device
Note:
The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
ALARM
RELAY
SPV
RELAY
TRBL
RELAY
Telephone
Line A
Connection
DC IN
EOL
To GSM/GPRS
Typical Installation in Canada
Line 2
Line 1
PCS-100
P
O
W
E
R
2
4
V
G
N
D
P
G
M
4
G
N
D
1
4V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
PGM4
AUX SUPPLY
+
-
+
-
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP : X.X.X.X
External IP : X.X.X.X
SG-Systems
Console 2.1
Default Gateway : X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
NO
C
NO
C
NO
C
COM
Z3
Z2
Z1
T
1
R
1
(-)
(+)
Conventional input
configured as 3G4010
radio trouble
FA-300
3G4010 TRBL
3G4010
C.O.
C.O.
FA-300 - 3G4010 Connection - Typical Diagram
Router
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010: 18 m max.
Contact DSC to reprogram the zone inputs to match
the FACP as shown in this diagram
-
i