Configuration with the CFG-300 LCD Service Tool
11.11.4 Command Menu/Dialer Config-->Time Parameters
Command Menu/Dialer-Config/Report Options
5.Fire Panel type
[X] FA-300 Panel->Default
[ ] FA-1000 Panel
[ ] FX-2000 Panel
Do not change this function;
keep it as default.
For factory use only.
Command Menu/Dialer-Config/Report Options
6.Dialer operation mode
[X] (U)DACT ->Default
[ ] DACT
Use this menu to select the
functionality of the dialer. In
DACT mode only common
trouble/alarm/supervisory
are reported while in
UDACT mode all point
information is reported
Command Menu/Dialer-Config/Report Options
7.Checksum Bits
[X] 8 Bit ->Default
[ ] 16 Bits
Do not change this function;
keep it as default
For factory use only.
Note:
Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Command Menu/Dialer-Config/Time Parameter
1.AC Loss delay
0 ->Default
Use this menu to delay the
reporting of AC loss trouble
on the dialer for the
programmed time period.
F i r e P a n e l T y p e :
[ X ] F A - 3 0 0 P a n e l
D i a l e r O p e r . M o d e :
[ X ] ( U ) D A C T
C h e c k s u m B i t s :
[ X ] 8 B i t s
i
1 A C - L o s s D e l a y
2 C e l l p h o n e D a t e
3 A u t o - T e s t T i m e
- T i m e P a r a m e t e r -
A C - L o s s D e l a y ( H r s )
0