76
9-4. Sequential mode
The sequential mode includes the sequential batching mode and the sequential discharge mode.
Moreover, Supplementary batching, Initial batching, Nuzzle batching and automatic free flow
compensation can be set if necessity requires.
9-4-1. Sequential batching mode
The sequential batching mode is a mode to control the measurement sequence depending to the
increased value of measuring value when the raw material is batching in.
Judgment condition
Status display
Judgment condition
Z-BAND
|Gross weight or (Net weight) |
≦
ZERO BAND (SET7).
F. FLOW
Net weight
≧
[Final (SET1) – Prelim 2 (SET4) ]
M. FLOW
Net weight
≧
[Final (SET1) – Prelim 1 (SET3) ]
D. FLOW
Net weight
≧
[Final (SET1) – Free Fall (SET2) ]
UNDER
Net weight
<
[Final (SET1) – Under (SET6)]
OVER
Net weight
>
[Final (SET1) + Over (SET5)]
OK
[Final (SET1) – Under (SET6)
≦
Net weight
≦
Final (SET1) + Over (SET5) ]
Operating explanation
1) When the start signal is input, the Full flow, Medium flow and Dribble flow will be ON.
Moreover, tare weight cancellation is provided with the input of start signal with the setting at the
same time.
2) When the net weight becomes [Final value – Prelim 2], the output of Full flow becomes OFF.
3) When the net weight becomes [Final value – Prelim 1], the output of Medium flow becomes OFF.
4) When the net weight becomes [Final value – Free Fall], the output of Dribble flow becomes OFF.
●
The comparative target of near zero can be selected from Gross weight and Net weight.
●
The near zero will become simple comparison operation.
●
The Full flow, Medium flow and Dribble flow will never become ON until the next start signal will be
input, once it becomes OFF.
●
Under, Over and OK can be operated with Net weight.
The comparison operation can be changed to simple comparison.
●
At the time of setting [Prelim 2=0], the Full flow becomes OFF and at the time of setting [Prelim 1=0],
Medium flow becomes OFF.
●
When making the automatic tare cancellation at the time of flow start, set to [Effective] for
[Automatic tare cancellation at the time of flow start] after referring to [9-9. Function of the SQ
function data].
Renewing the output of each condition display is synchronizing with A/D sampling.
Summary of Contents for CSD-903-EX
Page 1: ...DIGITAL INDICATOR CSD 903 EX Instruction Manual EN294 1492 H ...
Page 2: ...IV ...
Page 91: ...75 ...
Page 93: ...77 ...
Page 95: ...79 ...
Page 97: ...81 ...
Page 199: ...183 Inform us about the contents of failure and situation at site in details ...
Page 204: ...188 Inform us about the contents of failure and situation at site in details ...
Page 206: ...190 Inform us about the contents of failure and situation at site in details ...
Page 209: ...193 Inform us about the contents of failure and situation at site in details ...
Page 224: ... ...
Page 225: ......