96
10-7. Setting for operation at the time batch start
10-7-1. Start above near zero at the time of batch start
The operation when input batch start signal with measurement value is exceeded [ZERO BAND] is
selected by SQ function SQF-15.
When the [Start above near zero at the time of batch start] is set as [Invalid], measurement value is
exceeded [Near zero], batching will not be made due to the occurrence of error with the input of batch.
Default is set to [Invalid].
10-7-2. Automatic tare at the time of batch start
The operation of Automatic tare at the time of batch start is selected by SQ function SQF-16.
Default is set to [Invalid].
10-7-3. Batch start delay timer
Set the waiting time from the input of Batch start signal to the start of Batch at SQ function SQF-17
Setting range: 0000-9999, Unit: 1s, 0000: OFF
Default is set to [0000]
10-7-4. Automatic tare after batch start delay timer
The operation of Automatic tare after batch start delay timer is selected by SQ function SQF-18.
Default is set to [Invalid].
10-8. F-flow compare stop timer
Set the inhibiting time to compare the set value of F-FLOW and measured value at the time of start
of Batching.
Setting range: 0000-9999, Unit: 0.01s, 0000: OFF
Default is set to [0000].
10-9. M-flow compare stop timer
Set the inhibiting time to compare the set value of M-FLOW and measured value at the time of
finishing the F-FLOW.
Setting range: 0000-9999, Unit: 0.01s, 0000: OFF
Default is set to [0000].
10-10. D-flow compare stop timer
Set the inhibiting time to compare the set value of D-FLOW and measured value at the time of
finishing the M-FLOW.
Setting range: 0000-9999, Unit: 0.01s, 0000: OFF
Default is set to [0000].
Summary of Contents for CSD-903-EX
Page 1: ...DIGITAL INDICATOR CSD 903 EX Instruction Manual EN294 1492 H ...
Page 2: ...IV ...
Page 91: ...75 ...
Page 93: ...77 ...
Page 95: ...79 ...
Page 97: ...81 ...
Page 199: ...183 Inform us about the contents of failure and situation at site in details ...
Page 204: ...188 Inform us about the contents of failure and situation at site in details ...
Page 206: ...190 Inform us about the contents of failure and situation at site in details ...
Page 209: ...193 Inform us about the contents of failure and situation at site in details ...
Page 224: ... ...
Page 225: ......