12
2-4. Connection of standard RS-485 interface
Connect with A, B and S.G. on the output terminals for RS-485 interface and the 2 wire serial
interface showing as below figure. Refer to [14-4.Connecting method] as to the connection.
With the standard RS-485, either the command mode or the protocol conforming to the Modbus is
selectable.
(Refer to [15.Modbus communication] as to the Modbus communication.)
・
Stripped length of electrical cable tip is 7 mm.
・
The tightening torque of terminal screws on the terminal block is 0.6 N
・
m.
・
Please use AWG28 ~ AWG16 for connecting cable.
・
The signal ground of standard RS-485 interface and internal common are connected.
・
Please connect the shield with F.G. terminal of RS-485 interface / 2-wires method serial interface
terminal by using the shielded cable when CSD-903 complies with the CE conformity or applied JIS
standard.
A
Differential I/O (
+
)
B
Differential I/O (
-
)
S.G. Signal
ground
Screw side of terminals
Applicable Plug : XW4B-06B-H1.made by OMRON.