7.2.6
Example: reading the gross weight
Input range (MISO)
Byte
Value
Description
0
1
2
3
4
08
Read the gross weight (for func-
tion number 8, see Chap-
ter
)
5
6
7
Output range (MISO)
Byte
Value
Description
0
00
Gross weight - byte 0 (MSB)
1
00
Gross weight - byte 1
2
04
Gross weight - byte 2
3
D2
Gross weight - byte 3 (LSB)
4
08
Gross weight request detected.
5
Write
Active
Power
Fail
6
Cmd
Busy
Cmd
Error
Tare
Active
Cal Ac-
tive
Test
Active
7
OutOf
range
Stand-
still
Inside
ZSR
Center
Zero
Below
Zero
Over-
load
Above
Max
ADU
Error
In direct access, status bits are
independent of the write or read
request.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
The gross value (hex:000004D2 <=> 1234) can be read from bytes 0
3.
Negative values are output in the second complement.
7.3
ProfiBus parameter numbers
All configuration and calibration data can be written in the transmitter or can be read
from it with the following parameters.
The rest of the parameters belong to the advanced configuration, which can be found on
separate pages.
Values marked as (factory settings) are data in the original condition as delivered from
the factory.
One parameter always uses 4 bytes (DINT format)
7 ProfiBus interface
Transmitter Series PR 5211
EN-73
Minebea Intec