[Analog error]
The following settings are possible:
hold
In case of error the analog output keeps the last value.
0 mA
In case of error the analog output goes to 0 mA.
4 mA
In case of error the analog output goes to 4 mA.
20 mA
In case of error the analog output goes to 20 mA.
[ADU < 0]
Behavior when the weight value is below zero. The following settings are possible:
linear
In case of negative weight the analog output continues (only possible,
if the output value for zero weight is greater than 0 mA)
0 mA
In case of negative weight the analog output goes to 0 mA.
4 mA
In case of negative weight the analog output goes to 4 mA.
20 mA
In case of negative weight the analog output goes to 20 mA.
[ADU < FSD]
Behavior when the weight value is above Full scale deflection (FSD). The following
settings are possible:
linear
In case of weight value above FSD the analog output continues (only
possible, if the output value for FSD is less than 20 mA)
0 mA
In case of weight value above FSD the analog output goes to 0 mA.
4 mA
In case of weight value above FSD the analog output goes to 4 mA.
20 mA
In case of weight value above FSD the analog output goes to 20 mA.
[Analog value]
The analog output can be set to a fixed analog value. The analog mode has to be set to:
[transparent].
If the PLC has written the analog value, it is displayed on the screen [Parameter] Tool.
[Weight value for 0/4 mA]
Enter the weight value at which the analog output shall show 0 mA (or 4 mA, if the analog
range is set to 4 … 20 mA).
[Weight value for 20 mA]
Enter the weight value at which the analog output signal shall show 20 mA.
[ProfiBus address]
The address on the ProfiBus has to be defined here, valid addresses are in the range 1, 2 …
126, Default: 10.
[Bus size]
The normal bus size is 8 bytes.
10 byte bus size is required for a coded data transfer.
Default: 8.