2.4.1
Installation
The device is designed for mounting rail installation (35 mm, as per DIN 46277).
NOTICE
Excessive heat may reduce the device lifetime.
When mounting on the rail, make sure that the distance from other instruments left
and right of the device is at least 20 mm.
The device has to be installed in an EMC-compliant manner, see Chapter
.
2.4.2
Supply voltage connection
The supply voltage is 24 V DC +10 %/-15 %.
The maximum power consumption is 8.2 W.
For a connection to 230/115 V alternating current, an external power supply is required.
2.4.3
Protective ground connection
The protective ground connection is made via the support rails.