18
Installation
Line fuses
Minarik drives require fuses for protection. Use fast acting
fuses rated for 250 VAC or higher, and approximately 150%
of the maximum armature current. Fuse only L1 when the line
voltage is 115 VAC. Fuse both L1 and L2 when the line
voltage is 230 VAC.
Table 2 lists the recommended line fuse sizes.
Table 2. Recommended Line Fuse Sizes
90 VDC Motor
180 VDC
Max. DC Armature
AC Line Fuse
Horsepower
Horsepower
Current (amps)
Size (amps)
1/20
1/10
0.5
3
1/15
1/8
0.8
3
1/8
1/4
1.5
5
1/6
1/3
1.7
5
1/4
1/2
2.6
8
1/3
3/4
3.5
8
1/2
1
5.0
10
3/4
1 1/2
7.6
15
1
2
10
20
Minarik Corporation offers two fuse kits: part number
050–0069 (3–8A Fuse Kit) and 050–0073 (5–20A Fuse Kit).
Both fuse kits include a 1/2A pico fuse (part number
050–0064) which protects the transformer and logic.