PL-565
Accumass BW500
Page 77
Par
am
et
e
rs
e.g.
1
st
batch
2
nd
batch
3
rd
batch
setpoint
1000
1000
1000
pre-act
1000
950
960
total
1050
990
1000
P569
Manual Batch Pre-Act Amount
Enter a value to make the setpoint relay change state at a known value lower than
the setpoint (P564).
e.g.
Setpoint = 1000
Manual Pre-Act = 50
The setpoint relay will activate when the batch totalizer reaches 950.
P598
Span Adjust Percentage
Accessible only through manual span adjust (P019), when percent change (1) is
selected.
Refer to % Change on page 42.