Page 124
Accumass BW500
PL-565
Communic
a
tion
Type
Description
Start
# R
Parameter
Values
Read
reference
Format
Format Word for 32 bit
variables
40,062
1
0-1
r/w
see p. 125
ID
Device Identifier
40,064
1
2
r
see p. 125
Parameter
40,090
1
0-999
r/w
Primary Index
40,091
1
0-9
r/w
Secondary Index
40,092
1
0-9
r/w
Format Word
40,093
1
bit mapped
r/w
Read Value (word 1)
40,094
2
32 bits
r
Handshaking Area
(Parameter
Access)
Write Value (word 1)
40,096
2
32 bits
r/w
see p. 125
YYYY
41,000
1
1996-2069
r/w
MM
41,001
1
1 – 12
r/w
DD
41,002
1
1 – 31
r/w
see P008, p. 59,
and p. 127
hh
41,003
1
00 – 23
r/w
mm
41,004
1
00 – 59
r/w
ss
41,005
1
00 – 59
r/w
see P009, p. 59
and p. 127
Date and Time
Time Zone
41,006
1
-12 – 12
r/w
see P739, p. 83
Rate
41,010
2
32 bits
r
Load
41,012
2
32 bits
r
Speed
41,014
2
32 bits
r
Total 1
41,016
2
32 bits
r
Total 2
41,018
2
32 bits
r
see p.127
Device State
41,020
1
bit mapped
r
see p. 128
Command Control
41,022
1
bit mapped
r/w
see p. 129
Multi-Span Selection
41,024
1
1-4
r/w
see p. 50, and
P365 on pg. 70
PID 1 Setpoint
41,040
2
32 bits
r/w
PID 2 Setpoint
41,042
2
32 bits
r/w
see P416, pg. 75
Batch Setpoint
41,044
2
32 bits
r/w
see P564, pg. 76
Process Values
Batch Prewarn Setpoint
41,046
2
32 bits
r/w
see P567, pg. 76
Discrete Inputs
41,070
1
bit mapped
r
Relay Outputs
41,080
1
bit mapped
r
mA Inputs
41,090
2
0000 – 20,000
r
I/O
mA Outputs
41,110
3
0000 – 20,000
r
see p. 129
Diagnostic
Diagnostic State
41,200
1
number code
r
see p. 138
PID 1 Proportional Term
41,400
2
32 bits
r/w
PID 2 Proportional Term
41,402
2
32 bits
r/w
see P405, p. 73
PID 1 Integral Term
41,404
2
32 bits
r/w
PID 2 Integral Term
41,406
2
32 bits
r/w
see P406, p. 74
PID 1 Derivative Term
41,408
2
32 bits
r/w
PID 2 Derivative Term
41,410
2
32 bits
r/w
see P407, p. 74
PID 1 Feed Forward Term
41,412
2
32 bits
r/w
PID 2 Feed Forward Term
41,414
2
32 bits
r/w
see P408 p. 74
PID 1 Remote Setpoint Ratio
41,416
2
32 bits
r/w
PID Tuning
PID 2 Remote Setpoint Ratio
41,418
2
32 bits
r/w
see P418, p. 75
Summary of Contents for ACCUMASS BW500
Page 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Page 6: ...Page 6 Accumass BW500 PL 565...
Page 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Page 28: ...Page 28 Accumass BW500 PL 565 Installation...
Page 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Page 94: ...Page 94 Accumass BW500 PL 565 Operation...
Page 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Page 110: ...Page 110 Accumass BW500 PL 565 Batching...
Page 112: ...Page 112 Accumass BW500 PL 565 Certification...