Page 108
Accumass BW500
PL-565
Certification
Programming
The pre-warn function is optional.
The setpoint associated with the pre-warn relay is entered in P564, batch setpoint.
The setpoint associated with the batch relay is entered in P567, batch pre-warn
setpoint.
relays:
access P100, relay function
select relay (1 – 5)
select function 7, pre-warn
access P100, relay function
select relay (1 – 5, other than the pre-warn relay)
select function 8, setpoint
batch operation:
access P560, batch mode control
select 1, enable batch operation
access P564, batch setpoint
enter the desired batch total
access P566, batch pre-warn
set to
on
(1) or leave
off
(0)
if batch pre-warn selected,
access P567, batch pre-warn setpoint
enter the pre-warn total
access P568, batch pre-act,
set to off (0), Auto (1), or Manual (2)
Summary of Contents for ACCUMASS BW500
Page 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Page 6: ...Page 6 Accumass BW500 PL 565...
Page 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Page 28: ...Page 28 Accumass BW500 PL 565 Installation...
Page 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Page 94: ...Page 94 Accumass BW500 PL 565 Operation...
Page 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Page 110: ...Page 110 Accumass BW500 PL 565 Batching...
Page 112: ...Page 112 Accumass BW500 PL 565 Certification...