46
•
Jar statistics
The JAR STATISTICS report shows the volt and mhos/siemens results for jars with their measured
percentages of the reference value (%REF) you selected in BATTERY SETUP. (If you tested with-
out a reference value, dashes appear in reference
fi
elds.) If you tested both the jars and straps in
a string, the report shows resistance measurements (
μ
Ohm) for the strap in place of the percent-
age of the reference value. JAR STATISTICS appears only in the printout and prints after STRING
STATISTICS.
Low volts
warning (!)
In MHOS column:
4 with a ? to indicate that it is
below the WARN threshold
percentage of the reference
value (FAIL= !, WARN = ?)
The analyzer uses letter
designations if the jar has
more than one set of posts
A =
fi
rst set of +/–
posts tested on the jar
B = second set of +/–
posts tested on the jar
Results for
JARS AND STRAPS with 4 posts
In
μ
Ohm column:
Resistance
measurements in
microhms of strap
connections
JAR STATISTICS
JAR
VOLTS
MHOS
%REF
1
2.263
900
90%
2
2.262
890
89%
3
2.265
720
72%
4
!2.051
690?
69%
JAR STATISTICS
JAR
VOLTS
MHOS
μ
Ohm
J1A
2.011
224!
6
J1B
2.263
900
9
J2A
2.262
890
7
J2B
2.262
890
6
Results for
JARS
(if AC voltage/current ripple present)
JAR STATISTICS
JAR
VOLTS
MHOS
%REF
J1
2.263
900
90%
AC mV : 132
AC A : 2.2
J2
2.262
890
89%
AC mV : 40
AC A : 0.6
Results for
JARS ONLY (for a string of 12 V jars)
Chapter 7: Test results and reports