32
•
Using a reference value from the database
(BATTERY MANAGER)
If there is no reference value for the string you are testing, you can use a reference value for the jar
model in the BATTERY MANAGER database. The reference value is used only for this particular
test setup. If you want to permanently add a reference value or a new jar model to the database, see
“Adding jar model information to the database.”
1. Press the
ARROW
keys to highlight BATTERY MANAGER, and press
ENTER
.
2. Press the
ARROW
keys to highlight SELECT MANUFACTURER, and press
ENTER
.
3. Press the
ARROW
keys to highlight a manufacturer (or USER VENDOR for an unlisted
manufacturer), and press
ENTER
.
4. Press the
ARROW
keys
to highlight a model name.
5. Press
ENTER
to accept.
Using
REFERENCE DEVELOPER
to calculate a reference value
If there is no reference value for the string you are testing, you can use REFERENCE DEVELOPER
to calculate a value based on an average of the top 30% of the jars in the string, or on a percentage
of your choice.
1. Press the
ARROW
keys to highlight BATTERY MANAGER, and press
ENTER
.
2. Press the
ARROW
keys to highlight REFERENCE DEVELOPER, and press
ENTER
.
3. Press
ENTER
to accept the default, or press the
ARROW
keys (or use the numeric keypad)
to select the percentage of jars in the string.
4. Press
ENTER
to accept.
Selecting a
REFERENCE
value
This setting uses the manufacturer’s reference value for the model of jar selected in Battery Man-
ager. If you use REFERENCE DEVELOPER, the setting displays asterisks (
*****
) and cannot be
changed. The range is 0 (test without a reference value) to 20,000 . If you test without a reference
value, dashes appear in reference
fi
elds on the display and in the test results.
1. Press the
ARROW
keys to highlight REFERENCE, and press
ENTER
.
2. Press the
ARROW
keys (or use the numeric keypad) to select a value.
3. Press
ENTER
to accept.
Chapter 5: Selecting test parameters