40
•
Selecting the last used test setup with the
TEST
option
If you select the TEST option in the Main Menu and connect to a battery, the analyzer tests using the
parameters from your last test setup or, if there is no setup in memory, the default parameters.
Using the
OPEN
option
The OPEN option enables you to view the parameters of a saved test setup. You can also use OPEN
to change any parameters
EXCEPT
:
JARS ONLY / JARS & 1 STRAP / JARS & 2 STRAPS
POSTS PER JAR
JARS PER STRING
VOLTS PER JAR
VOLT & CONDUCTANCE / VOLTAGE ONLY / VOLTS THEN CONDUCT(ANCE)
If you change these parameters you will erase the string’s test data. If you need to change them, use
the NEW (TEST) function and save the setup.
To use the OPEN option:
1. Press the
ARROW
keys
to highlight the BATTERY SETUP icon in the Main Menu, and press
ENTER
.
2. Press the
ARROW
keys
to highlight the OPEN icon in the BATTERY SETUP menu, and press
ENTER
.
3. Press the
ARROW
keys
to select a test setup, and press
ENTER
.
4. The analyzer will alert you that testing for that string was completed:
TESTING OF STRING
IS COMPLETE
TO SET UP AND TEST A
NEW STRING, PRESS ‘C’
THEN SELECT ‘NEW’
5. Scroll through the list and verify or change parameters.
6. Scroll to SAVE AND CONTINUE to exit or SAVE AND TEST to test a string.
NOTE:
If you are not connected to the jar, the analyzer prompts you to connect. Connect the
clamps or probes, and press
ENTER
to start the test.
IMPORTANT:
If you are measuring VOLTS THEN CONDUCTANCE, disconnect from the last
jar in the string after the voltage test. Reconnect to the
fi
rst jar and press
ENTER
to test for
conductance. (The analyzer displays TESTING JAR 1 when you reconnect.)
The analyzer beeps twice when the test is done. The analyzer beeps longer if:
•
the conductance value is below the reference value
•
the percentage of the reference is below the values for WARN or FAIL
•
the voltage level is below the LOW VOLTS value
Chapter 6: Testing