Air-cooled modular chiller unit 50Hz
Minimum and Maximum water flow rates
Item
Water flow rate(m3/h)
Model
Minimum
Maximum
0&&+$7$6/
4.68
5.72
0&'+$7$6/
4.68
5.72
0&&+$6$/
10.08
12.32
0&&'$6$/
10.08
12.32
0&&+$6$/
18.54
22.66
0&&+$6$
27.9
34.1
0&&+$6$7
38.7
47.3
1
.2.10 Design of the store tank in the system
a. kW is the unit for cooling capacity, L is the unit for (G) minimum water flow volume in the formula.
Comfortable type air conditioner
G= cooling capacity×2.6L
Process type cooling
G= cooling capacity×7.4L
b. In certain occasion (especially in manufacture cooling process), for conforming the system water content
requirement, it‟s necessary to mount a tank equipping with a cut-off baffle at the system to avoid water
short-circuit, Please see the following schemes:
Error
Recommendation
Fig.4-4
Error
Recommendation
1
.2.11Design of expansion tank
If a closed expansion tank with its filled volume of air is too small, the system pressure will easily exceed the