Air-cooled modular chiller unit
56
Heating:
Hot water
outlet temp.
Ambient temp.(
℃
)
-10
-6
-2
2
7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
℃
)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
40.00
85.78
26.91
107.22
30.57
126.14
33.97
140.16
36.93
152.34
38.87
170.63
38.33
196.22
41.39
41.00
82.89
27.45
103.75
31.20
122.20
34.66
135.93
37.68
147.91
39.66
165.36
39.11
189.83
42.24
42.00
80.50
28.01
100.87
31.83
118.96
35.37
132.47
38.45
144.30
40.47
161.04
39.91
184.55
43.10
43.00
78.55
28.59
98.56
32.48
116.37
36.09
129.73
39.23
141.47
41.30
157.60
40.72
180.29
43.98
44.00
77.03
29.17
96.78
33.15
114.39
36.83
127.67
40.03
139.38
42.14
154.99
41.55
177.00
44.88
45.00
75.92
29.76
95.49
33.82
113.01
37.58
126.27
40.85
138.00
43.00
153.18
45.58
174.63
49.23
46.00
74.43
30.06
93.74
34.16
111.07
37.96
124.24
41.26
135.93
43.43
150.61
46.04
171.39
49.72
47.00
72.23
30.66
91.09
34.85
108.05
38.72
121.00
42.08
132.53
44.30
146.58
46.96
166.52
50.71
48.00
69.38
31.58
87.60
35.89
104.04
39.88
116.64
43.35
127.89
45.63
141.19
48.37
160.11
52.23
49.00
65.61
32.85
82.94
37.33
98.62
41.47
110.69
45.08
121.50
47.45
133.89
50.30
151.56
54.32
50.00
61.38
34.49
77.70
39.19
92.50
43.55
103.93
47.33
114.21
49.83
125.63
52.81
141.96
57.04
Note:
The inlet/outlet water temperature difference is 5
℃
.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...