Air-cooled modular chiller unit
Foreign matter in the chilled water system will adversely affect the heat transfer capability of the evaporator,
and could increase the pressure drop and reduce the water flow. To provide optimum unit operation, proper
water treatment must be maintained. Refer to the able as following.
Fouling Factor
ALTITUDE
(m)
Difference of water
inlet and outlet temp.
(
℃
)
Fouling Factor
0.018
℃
/kW
0.044m 2
℃
/kW
0.086m 2
℃
/kW
0.172m 2
℃
/kW
C
P
C
P
C
P
C
P
Sea level
3
1.036
1.077
1.019
1.076
0.991
0.975
0.963
0.983
4
1.039
1.101
1.022
1.080
0.994
0.996
0.971
0.984
5
1.045
1.105
1.028
1.086
1.000
1.000
0.977
0.989
6
1.051
1.109
1.034
1.093
1.006
1.004
0.983
0.994
600
3
1.024
1.087
1.008
1.064
0.980
0.984
0.951
0.991
4
1.027
1.111
1.011
1.068
0.983
1.005
0.959
0.992
5
1.034
1.115
1.017
1.074
0.989
1.009
0.965
0.997
6
1.043
1.115
1.026
1.084
0.998
1.009
0.973
0.999
1200
3
1.013
1.117
0.996
1.052
0.969
1.011
0.942
1.002
4
1.015
1.118
0.998
1.055
0.971
1.012
0.948
1.003
5
1.023
1.122
1.006
1.063
0.979
1.015
0.955
1.005
6
1.031
1.125
1.015
1.072
0.987
1.018
0.962
1.007
1800
3
1.002
1.128
0.986
1.042
0.959
1.021
0.935
1.007
4
1.005
1.129
0.989
1.045
0.962
1.022
0.941
1.010
5
1.012
1.132
0.995
1.051
0.968
1.024
0.945
1.012
6
1.018
1.134
1.001
1.058
0.974
1.026
0.949
1.014
C--Cooling capacity
P--Power
1
.2.3 Installation & regulation guide for target flow controller
● Please carefully check flow switches before conducting installation of the target flow controller. Packing
should be in good condition, and the appearance should be free of damage and deformation. If any problem,
please contact the manufacturer.
● Flow switches can be installed in the horizontal pipeline or the vertical pipeline with upward flowing
direction but cannot be mounted in the pipeline with downward flowing direction. The inlet water of gravity
should be taken into account when flow switches are installed in the pipeline with upward flowing direction.
● Target flow controller must be installed on a section of straight-line pipeline, and its both ends must be
supplied with straight-line pipes whose length is at least 5 times diameter of the pipe. In the meanwhile, the
fluid flowing direction in the pipeline must be consistent with the direction of arrow on the controller. The
connection terminal should be located where wiring connection can be easily done.
● Pay attention to the following items when conducting installation and wire connection:
a. Collision of the wrench with the soleplate of the flow switch is prohibited, since such collision may cause
deformation and failure of the flow switch.
b. To avoid electric shock and damages to the devices, the power supply should be cut off, when wires are
connected or adjustment is done.
c. When wiring connection is conducted, adjustment of other screws except connection terminals of micro
switches and ground screws is prohibited. In the meanwhile, over great force should not applied when wires
of micro switches are connected, otherwise micro switches may suffer displacement, thus leading to failure
of flow switches.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...