Air-cooled modular chiller unit
Notice:
1) For installation of multi-module, the most modules should be not more than 8 modular units.
2) For installation of multi-module, please drill a dead hole(
Φ
9mm) at the total water outlet pipeline,
and move the total water effluent temperature sensor at No.0 address to the hole.
Table of diameter parameters of main inlet and outlet pipes for 30kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
DN40
DN100
30×1
30×9
30×2
30×10
DN65
30×3
30×11
DN125
30×4
30×12
30×5
30×13
DN80
30×6
30×14
30×7
30×15
30×8
30×16
Table of diameter parameters of main inlet and outlet pipes for 65kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
DN65
DN125
65×1
65×9
65×2
65×10
DN80
65×3
65×11
DN100
DN150
65×4
65×12
Less than 8 modules
65×5
65×13
65×6
65×14
DN200
65×7
65×15
DN125
65×8
65×16
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...