Air-cooled modular chiller unit
1
1
.1.3 New 30kW module PCB, outlook view (Available for
0&&+$7$6/
,
0&'+$7$6/
)
10 9 8 7
6 5
4
3
2
1
11
15
12
18
13
14
17
16
19
20
21 22 23 24 25 26 27
33
30
32
31
28
29
1
.1.4 New30kW module components description (Available for
0&&+$7$6/
,
0&'+$7$6/
)
No. Detail information
1
Detection of current of the compressor A1 (Protection code P4).
2
Detection of current of the compressor B1 (Protection code P5).
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is
detected to exceed protective value set (18A for constant speed compressor), it will be shut down and re-started after 3
min.
3
Power port for the current board
4
T4: outdoor ambient temperature sensor (Fault code E7).
T3B: pipe temperature sensor of the condenser B (Fault code E6 and protection code P7).
T3A: pipe temperature sensor of the condenser A (Fault code E5 and protection code P6).
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit. Start
outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the modular unit detects the temperature of the outdoor pipe T3A or T3B of the
system exceeds the protective temperature 65
℃
, the corresponding system will be shut down. And it will be re-started up,
after the temperature drops below the recovery temperature 60
℃
. Another system will be not affected.
1
Control System
1
.1 PCB Outline and Description
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...