Air-cooled modular chiller unit
77
1
1
Installation
1
1
.1 Unit Installation
1
1
.1.1 Transportation
The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit.
a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the
length of each rod must be more than the outer frame of the base and suitable for balancing of the unit.
b. Lifting: the strength lifting rope (belt) can bear should be 4 times the weight of the unit. Check the lifting
hook and ensure that it is firmly attached to the unit, and the lifting angle should be more than 60º. To avoid
damages to the unit, the contact position of the unit and lifting rope should be provided with an at least
50mm thick wood block, cloth or hard paper. Any person is not allowed to stand below the unit when lifting it.
30kW module
Handling of the unit
The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit.
a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the length of each rod must be
more than the outer frame of the base and suitable for balancing of the unit.
b. Lifting: the strength lifting rope (belt) can bear should be 4 times the weight of the unit. Check the lifting hook and ensure that it is
firmly attached to the unit. To avoid damages to the unit, the contact position of the unit and lifting rope should be provided with an at
least 50mm thick wood block, cloth or hard paper. Any person is not allowed to stand below the unit when lifting it.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...