Air-cooled modular chiller unit
1
4
Weight
Net weight
kg
1150
Operation weight
kg
1270
Power wire
mm
2
×No.
35×3+16×2
Signal wire
mm
2
×No.
Control type
Safety protection device
Noise level(semi-anechoic)
dB(A)
74
Operation water temp
Cooling
:
0
〜
17
(
Less than 5
°C
must add
antifreeze
)
Heating
:
22
〜
50
Ambient temp
Cooling
:
-10
〜
46
Heating
:
-10
〜
21
Wired controller
0.75x3-core
°C
°C
1) Protection for
over-high discharge
pressure.
2) Protection for over-low
suction pressure.
3) Power supply phase
sequence protection.
4) Anti-freezing
protection in cooling
mode.
5) Anti-freezing
protection in Winter.
6) Protection for
compressor over current.
7) Protection for
compressor overload.
8) Outlet and inlet water
temperature difference
protection.
9) Compressor discharge
temperature protection.
10) Water flow cut-off
protection.
11) Sensor malfunction
protection.
12) Low ambient
temperature drive-up
protection
13) Low-temperature
protection of shell and
tube heat exchanger.
Note:
Please refer to the water flow volume in the above table strictly to design and install.
All the above data is measured base on the following working condition:
1. Cooling mode: water side fouling factor: 0.086m2·°C/kW, chilled water inlet/outlet: 12°C / 7°C, and outdoor ambient temp. of
35°C DB.
2. Heating mode: water side fouling factor: 0.086m2·°C/kW, warm water inlet/outlet: 40°C / 45°C, and outdoor ambient temp.
7°C DB/6°C WB.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...