Air-cooled modular chiller unit
1
19
COM (O) 485 communication port (Fault code E2).
20
Anti-freezing pressure protection of the system A(Protection code Pc).
Anti-freezing pressure protection of the system B(Protection code Pd).
21
The alarm signal output of the unit(ON/OFF signal).
22
Auxiliary electric heater:
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-240V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45
℃
, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50
℃
, the
switch will be opened, and the auxiliary electric heater will stop working.
23
PUMP:
Attention: the control port value of the pump actually detected is ON/OFF but not 220-240V control power supply, so special
attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
24
Factory setting
S2 ON: Cooling only OFF
:
R&C
S3 ON: Digital OFF
:
Fixed
S4 ON:H-EEprom OFF
:
Normal
S5 ON:C-Eeprom OFF
:
Normal
25
One compressor of the system B.
Four-way valve of the system B.
One compressor of the system A.
Four-way valve of the system A.
26
8
9
A
B
C
D
E
F
8 7
6
5
4
3
2
1
0
0 1
2
3
4
5
6
7
8
F
E
D
C
B
A
9 8
ADDRRSS
Each modular part of modular unit has the same electric control function, and the main unit and subordinate units can be set
When the address is 0, it serves as the main unit.
When the address is 1,2,3……F, it serves as the
subordinate unit 1,2,3……15.
Summary of Contents for MCCDH30A-TA3SL
Page 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Page 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Page 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Page 41: ...Air cooled modular chiller unit 41 185 kW module...
Page 46: ...Air cooled modular chiller unit 46 130 kW module...
Page 48: ...Air cooled modular chiller unit 60 200kW module...
Page 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Page 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...