Line Driver Output Voltage (Register 0x214)
Register Address: 0x214
This parameter defines the output voltage level of the complementary line driver outputs.
The output voltage should be adjusted to the receiving device such as a VFD drive or similar.
0 = Outputs disabled
1 = 5V (typical 3.3V)
2 = 12V (typical 10.5Vl)
3 = 24V (Power Supply – 1.5Vl)
MODBUS commands:
Analog Output Select (Register 0x215)
Register Address: 0x215
T
he analog output on J1 is either a voltage or a current 4-20mA output. This parameter selects
which mode the output will operate at.
0 = Voltage Output
1 = Current 4-20mA Output
CAUTION
Connecting a voltage source to this output be sure to set this parameter
to current output. Otherwise the voltage output will attempt to drive
against the applied voltage source.
This parameter is protected and the unit must be set to Op-Mode 2 in order to affect this
setting.
MODBUS commands: