MICRONOR AG
MR340-1 DIN Rail Module Controller
Page 46 of 74
5
Unipolar output range of 4-24mA representing the absolute value of the
Counter. 4mA represents the zero position and 20mA corresponds to the
Current Scale setting (regardless of direction or sign).
Overrange extends over 20-23mA range.
6
Window mode with Output range of 4-24mA. 4mA represents zero and
negative position and 20mA corresponds to Current Scale.
Overrange extends over 20-23mA.
In all cases there is an overrange capability of 4mA to 23mA.
Use the MODE command to select the desired output mode.
Current Output Cautions…
•
Current outputs are inherently short circuit proof!
•
The maximum burden resistance for the MR340 is 500 Ohms with a
+24V power supply. At 23mA that represents a voltage drop of 12V.
•
To minimize internal heat dissipation we recommend that the user
inserts a ‘burden resistance’ to always assure at least 200 Ohm.