MICRONOR AG
MR340-1 DIN Rail Module Controller
Page 34 of 74
0x130
0x131
CHA Amplitude
minimum
1
n/a
Outputs the minimum observed
amplitude of the optical signal.
Generally this signal is less than 15
counts because the optical signal
should swing from 0 to 640counts. (0V
to 2V).
Of course the encoder must be
turning otherwise the signal can be
anything from 0 to +640.
0x131
0x132
CHA Amplitude
maximum
1
n/a
Outputs the maximum observed
amplitude of the optical signal.
Generally this is signal approximately
640 counts because the optical signal
should swing from 0 to 640counts. (0V
to 2V).
Of course the encoder must be
turning otherwise the signal can be
anything from 0 to +640.
0x132
0x133
Voltage Offset
Factory
Calibration
1
-128 – 127
Factory use only – do NOT write to it.
Hardware calibration value for voltage
output
0x133
0x134
Voltage Gain
Pos
Factory
Calibration
1
-128 – 127
Factory use only – do NOT write to it.
Hardware calibration value for voltage
output
0x134
0x135
Voltage Gain
Neg
Factory
Calibration
1
--128 – 127 Factory use only – do NOT write to it.
Hardware calibration value for voltage
output
0x135
0x136
Current Gain
Factory
Calibration
1
-128 – 127
Factory use only – do NOT write to it.
Hardware calibration value for current
output
0x136
0x137
CHB Amplitude
minimum
1
n/a
Outputs the minimum observed
amplitude of the optical signal.
Generally this signal is less than 15
counts because the optical signal
should swing from 0 to 640counts. (0V
to 2V).
Of course the encoder must be
turning otherwise the signal can be
anything from 0 to +640.
0x137
0x138
CHB Amplitude
maximum
1
n/a
Outputs the maximum observed
amplitude of the optical signal.
Generally this signal is approximately
640 counts because the optical signal
should swing from 0 to 640counts. (0V
to 2V).