Page 151
Error message
Meaning of the error message Measures
Main
index
Sub
index
59
1
FSM: Fail-safe mode
supply/safe pulse inhibitor
Cause: Internal error in module in failsafe
supply circuit section or in the driver
supply for the upper and lower
switches.
Action:
Module faulty, replace.
2
FSM: Logic failure /
intermediate circuit
Cause:
Reference voltage 2.5 V outside
tolerance.
Logic supply overv24 V
detected.
Action:
Module faulty, replace.
3
FSM: Error internal power
supply
Cause: Voltage (internal 3.3 V, 5 V, ADU
reference) outside the permissible
range.
Action:
Module faulty, replace.
4
FSM: Error management, too
many errors
Cause: Too many errors have occurred
simultaneously.
Action:
Clarify: What is the status of the
installed safety module - does it
contain a valid parameter set?
Read out and analyse the
permanent event memory of the
basic device via Metronix
ServoCommander®
Eliminate error causes step by step.
Install safety module with “delivery
status” and perform commissioning
of basic device.
If this is not available: Set factory
settings in the safety module, then
copy data from the basic device and
perform complete validation. Check
whether the error occurs again.
5
FSM: Log file - write error
Please contact the Technical Support.
6
FSM: Parameter set - save
error
Please contact the Technical Support.
Product Manual „Servo drives ARS 2100 SE“
Version 5.0