![Metronix 9200-4104-2000 Mounting Instructions Download Page 70](http://html.mh-extra.com/html/metronix/9200-4104-2000/9200-4104-2000_mounting-instructions_1780033070.webp)
6 Technical data
Time
Description
Value
t
K1
Delay between the switching of S1 and the
closing of the undelayed contact K1
See the data sheet of the
safety relay
t
K1_delay
Delay between S1 and the opening of the off-
delayed contacts K1
Can be adjusted on the
safety relay
t
STOA/B OFF
STOA/B – switching time from high to low
See also section
output stage inactive and maximum OSSD
test pulse duration
Maximum response time
5 ms
t
STOA/B ON
STOA/B – switching time from high to low
0.6 ms typ., 1 ms max.
t
DRV
Delay of the internal sequence control of the
servo drive
10 ms max.
t
ENAB HI
Time that DIN5 must be low after STOA/B
has been reactivated and the status of the
STO circuit has changed
>
20 ms
t
A
Switch-off delay of the holding brake
Parameterisable
1
t
F
Switch-on delay of the holding brake
Parameterisable
1
1
see section
Brake control and automatic brake
in the Product manual smartServo BL 4000-D /
smartServo BL 4000-M
Mounting Instructions BL 4000-M and BL 4000-D
Page 70 of 95
Summary of Contents for 9200-4104-2000
Page 89: ...9 Appendix BL 4800 M BL 4800 D Mounting Instructions BL 4000 M and BL 4000 D Page 89 of 95 ...
Page 91: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 91 of 95 ...
Page 93: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 93 of 95 ...
Page 94: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 94 of 95 ...
Page 95: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 95 of 95 ...