MI 2893 / MI 2892 / MI 2885
Measurement Setup submenu
124
Record Start
Time
Selection Recorder Start Time:
Rounded – recorder start is postponed and synchronized with the clock
(integer periods in one-hour period)
Immediately – recorder starts on the next minute
Transient select
N/GND
Transient selection measurement between Phase - Neutral or Phase – Ground (MI
2893 only)
Table 107: Keys in Measuring Methods setup screen
Toggles between given parameters.
Changes selected parameter.
Returns to the “MEASUREMENT SETUP” submenu.
3.23.7
Transient setup
Note:
MI 2893 – Transient Recorder runs simultaneously with General Recorder
MI 2892/MI 2885 – Transient Recorder runs as independent recorder (could not run simultaneously
with General Recorder).
In this menu parameters for transient trigger could be selected. It is possible to select trigger for:
-
Phase voltage,
-
Phase current,
-
Neutral voltage,
-
Neutral current.
Two different types of trigger could be defined:
-
Selection to the voltage/current level,
-
Envelope.
Figure 93: Transient setup screen – MI 2893