MI 2893 / MI 2892 / MI 2885
Flickers
63
3.9.2
Trend
During active recording TREND view is available (see section 3.14 for instructions how to start recording).
Flicker parameters can be observed by cycling function key F4 (METER -TREND). Note that Flicker meter
recording intervals are determinate by standard IEC 61000-4-15. Flicker meter therefore works
independently from chosen recording interval in GENERAL RECORDER.
Figure 45: Flickers trend screen
Table 33: Instrument screen symbols and abbreviations
Pst1m1,
Pst1m2,
Pst1m3,
Pst1m12,
Pst1m23,
Pst1m31
Maximal ( ), average ( ) and minimal ( ) value of 1-minute short term flicker
P
st(1min)
for phase voltages U
1
, U
2
, U
3
or line voltages U
12
, U
23
, U
31
Pst1,
Pst2,
Pst3,
Pst12,
Pst23,
Pst31
Maximal ( ), average ( ) and minimal ( ) value of 10-minutes short term
flicker P
st
for phase voltages U
1
, U
2
, U
3
or line voltages U
12
, U
23
, U
31
Plt1,
Plt2,
Plt3,
Plt12,
Plt23,
Plt31
Maximal ( ), average ( ) and minimal ( ) value of 2-hours long term flicker P
lt
in phase voltages U
1
, U
2
, U
3
or line voltages U
12
, U
23
, U
31
Table 34: Keys in Flickers (TREND) screens