MI 2087 Instaltest 61557
Measurement instructions
22
Step 4
•
Connect test leads
to tested object according to the figures below.
Fig. 15.
Connection of Universal Test Cable and optional Probe Test Lead
(Order No.
A 1012
)
Fig. 16.
Connection of optional Tip Commander (Order No.
A 1002
) and optional
Probe Test Lead (Order No.
A 1012
)
Step 5
•
Press the
START
key and release it. Measurement will be carried out and result
displayed afterwards. Each measurement is accomplished in two steps (polarity
is reversed between the two steps automatically). Higher partial result is
displayed. The result, if lower than set High limit value, will be equipped with
beep sound signal.
•
Check lower partial result, pressing the
DISPLAY
key.
•
Store displayed result for documentation purpose; see instructions how to store
it in chapter 4.1. Storing of test results.
PCC1
PCC2
PCC3
MPEC
Option A 1012
Option A 1002
PCC1
Option A 1012
PCC2
PCC3
N/L2
PE/L3
L/L1
MPEC
MPEC..........Main Potential
Equilizing Collector
PCC.............Protection Conductor
Collector