MI 2087 Instaltest 61557
Measurement instructions
25
Fig. 18.
Connection of Universal Test Cable
Fig. 19.
Connection of optional Tip Commander (Order No.
A 1002
)
•
Press the
START
key again after finishing the measurement, last result will stay
displayed. The result cannot be stored (just auxiliary result).
Notes!
•
In case of present external voltage higher than 9 V a.c./d.c. between test
terminals, the Continuity measurement will not start after pressing
START
key,
but the voltage will be displayed, equipped with
“!”
mark! Beep warning sound
will be affected too.
•
If test result is out of measurement range (open test leads),
>1999
Ω
Ω
Ω
Ω
message
will be displayed!
•
Positive pole of test voltage is attached to blue test lead (Universal test cable) or
to commander test tip (Tip Commander)!
•
Compensation of test leads, affected in Continuity of Protective Conductors
function, will be considered in this function too.
•
bat
message, displayed during or after finishing the measurement means
batteries are too weak to guarantee correct result. Replace the batteries.