MI 3311 GammaGT
Technical specifications
16
3.3 Substitute leakage current
Range Resolution Accuracy
0.00 mA
9.99 mA
0.01 mA
10.0 mA
20.0 mA
0.1 mA
(5 % of r 3 digits)
Open circuit voltage .................. <50 V AC at rated mains voltage
Short circuit current................... <2,5 mA
Pass levels:
Substitute leakage .................... 0.25 mA, 0.50 mA, 0.75 mA, 1.00 mA, 1.50 mA, 2.00 mA,
2,25 mA, 2.50 mA, 3.50 mA, 4.00 mA, 4.50 mA, 5.00 mA,
5.50 mA, 6.00 mA, 7.00 mA, 8.00 mA,9.00 mA, 10.0 mA,
15.0 mA, ---- mA
Substitute leakage - P............... 0.25 mA, 0.50 mA, 0.75 mA, 1.00 mA, 1.50 mA, 2,00 mA,
--- mA
Test duration............................. 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s,
∞
Displayed current...................... calculated to appliance nominal mains supply voltage
(230 V) x 1.06.
Test terminals:
Sub. leakage
LN (mains test socket)
↔
PE ( mains test socket)
Sub. leakage-P
LN (mains test socket)
↔
S/EB1 (probe)
3.4 Polarity test
Test voltage .............................. <50 V AC
Detects...................................... PASS, L OPEN, N OPEN, PE OPEN, L-N CROSS,
MULTIPLE FAULT.
Test terminals:
Polarity
Main test socket
↔
IEC test socket
3.5 Voltage measurement
Range
Resolution
Accuracy
0
300 V
1 V
(2 % of r 2 digits)
Result type................................ True r.m.s. (trms)
Nominal frequency range.......... 0 Hz, 50 Hz
60 Hz
Frequency accuracy ................. Indication only
Test terminals:
Voltage TRMS
IEC test socket