A 1632
eMobility Analyser
Single tests
18
Test connection
Figure 5.10: Example of a Diagnostic test - Monitor
Measurement procedure
Connect the A 1631 cable adapter between the charging cable /station and the electrical
vehicle.
Connect test probes to A 1632 eMobility Analyser.
Select the Diagnostic test
– Monitor on the master instrument.
Set test parameters on the master instrument
Check that the eMobility Analyser is in Remote mode (Bluetooth communication between
eMobility Analyser and the master instrument is established).
Carry out the Diagnostic test.
Manually set status of the test (optional).
Save results (optional).
For information about test parameters and displayed results refer to Instruction manual of the
master instrument.
5.5 Diagnostic test
– CP Errors
This test can simulate typical errors (diode shorted, CP
– PE shorted, PE open) on the CP
signal. The disconnection time of the charging cable / station, as a reaction to the simulated
fault on the CP signal, is measured.
The test is performed in combination with an external (master) instrument. The results are
transmitted via Bluetooth and displayed on the master instrument.
Test connections
Refer to
for test connections.
Measurement procedure
Connect the charging cable /station to the eMobility Analyser (see
Select the Diagnostic test
– CP Error on the master instrument.
Set test parameters (CP error) on the master instrument.
Check that the eMobility Analyser is in Remote mode (Bluetooth communication between
eMobility Analyser and the master instrument is established).
Carry out the Diagnostic test.
Manually set status of the test (optional).
Save results (optional).
For information about test parameters and displayed results refer to Instruction manual of the
master instrument.